-15c Air Cooled Glycol Water Chiller with 20kw Cooling Capacity

-15c Air Cooled Glycol Water Chiller with 20kw Cooling Capacity

Brand:Topchiller

Minorder:1set

Port:Shenzhen Port

Packaging:Wooden Case

Place:China

Certification:CE,ISO,CCC,UL

Send Inquiry
 Model[TPL-**L]3A5A6A8A10A12A15A20AD25AD  30AD40A
Nominal Cooling 
capacity
-10ºCKW3.86.37.59.113.216.119.526.432.23952
-20ºC1.93467.1813.916.920.824.430.8
-30ºC11.61.92.73.23.86.19.512.114.319
 -35ºC0.671.041.52.32.834.36.358.310.113.35
EvaporatorCoolant
volume
-10ºCm3/h0.651.11.31.62.32.83.44.55.66.79
-20ºC0.330.520.691.11.231.381.382.853.574.25.3
-30ºC0.170.280.330.470.550.651.11.62.12.463.3
-35ºC0.120.180.260.40.480.520.721.11.431.742.3
Type
Shell and tube / SS plate heat exchanger
Pipe connectioninch11111-1/21-1/2222-1/22-1/23
Input powerkw3.184.865.617.259.410.913.518.822.5528.537.5
Power source
PH 380V~415V 50HZ
RefrigerantType
R22 / R404A
Control
Thermostatic expansion valve
CompressorType
Hermetic scroll(piston)
Motor Powerkw2.253.754.567.5911.37.5*29.37*211.3*230
CondenserType
Big volume & low noise axil fan + high efficiency finned cooper tube
PumpPowerkw0.750.750.750.751.11.11.52.22.245.5
Max. headM2020202020202020202520
Safety devicesInner thermostat for compressor motor, unit overload relay, high and low
pressure switch, freeze protection thermostat, reverser phase protection 
relay, discharge gas thermostat, flow switch
DimensionLengthmm9801120112013001500150017801950215021502650
Widthmm5606106106807607608509509809801200
Heightmm13201390139015301660166018001960210021002200
Net weightkg13517521031045053075083592010801125
Remarks:Cooling air inlet/outlet temperature 30ºC/38ºC.The design max running ambient temperature is 45ºC.Higher capacity pump is for option.Units for differe
Design features
-Water temperature range -35ºC to 20ºC.   
-Danfoss/Copeland scroll compressor. 
-For temperature below -15ºC, semi-hermetic piston type compressor will be adopted.
-Shell and tube evaporator, plate type for option.
-Microcomputer control system offering accurate temperature stability within ±1ºC.
-Low noise axial fan motor, quietly running.
-Large flow volume centrifugal pump, higher pressure available on request.
-Multi-protection devices to make sure the chiller and the equipment running safety.
-Schneider electrical components.
-Danfoss/Emerson thermal components.
Unit Safety Protection
-Compressor inner protection
-Over current protection
-High/low pressure protection
-Over temperature protection 
-Flow switch
-Phase sequence/phase missing protection
-Low coolant level protection
-Anti freezing protection 
-Exhaust overheat protection
Product parameter